Home : Product Database : Speciality Product Group : MT Tornado : MT Commissioning : MT Tornado General Settings
MT Tornado General Settings

MT Tornado General Details

Heat input gas

kW

45

Gas type

 

Propane G31

Gas category

 

I3p(37)

I3p(30)

Supply pressure

mbar

37

30

Nozzle pressure

mbar

16.0

Injector size

 

7x1.8

Electrical supply

V

230/110

Electrical input

W

400

Weight

kg

85

Hose (Ambi-Rad Part No 201308

 

1.2m lg, 10mm ID approved to

EN 1763-1 BS3212 (UK Only)

Regulator

kg/h

4

4

mbar

37

30

Min Room size

m3

510

Required ventilation

cm2

1275